Rate me

The transmission network in the National Electricity Market (NEM) is protected from overloads in times of events or during normal operation by nominating thermal ratings on primary elements (such as transmission lines and transformers), against which the real-time electricity flows should not be larger. This limitation is important in the safe operation of the power system as the chances of a transformer blowing up, or transmission lines arcing, are higher when flows are sufficiently high to heat up the conductors and make them sag.

Transmission Network Service Providers across the NEM issue the nominated safe levels of thermal ratings for each element in their jurisdiction. AEMO publishes that relevant information in the Transmission Equipment Rating which can be found here: AEMO | Transmission Equipment Ratings. In this Chart of the week, Saliw Cleto looks at how thermal ratings change from season to season for each jurisdiction in the NEM and provide a hypothesis on why they behave how they behave.

The Chart below shows the average ratio of the summer to the winter thermal rating across all lines and transformers for each region in the NEM, according to the Transmission Equipment Rating file from AEMO for ‘system-intact’ operation. It also shows the shoulder to winter thermal ratio. As transmission lines are rated differently, normalisation is needed to appropriately aggregate the figures . Winter rating is used as the base figure for each transmission element.

It can easily be seen from the Chart that the seasonal thermal rating ratio is lower in the southern states (Vic and Tas) compared to the other states in the NEM by a whopping 10% to 15%. This is not surprising as the biggest driver for thermal ratings is the ambient temperature, for which the Victoria and Tasmania have the biggest spread over a year. Note that, the higher the temperature, the lower the ratings, so summer thermal ratings are significantly lower than their winter thermal ratings. Unlike the northern states, where the temperature is generally warm across the year, Victorian weather is cold-ish most of the time, but when it gets warm during the summer period, the thermal rating falls down more severely. Note that in Victoria and Tasmania, ratings are defined for different ambient temperatures than for different seasons; hence, to be conservative, the shoulder ratings are taken to be similar to the summer ratings making the ratio for the summer-to-winter similar to shoulder-to-winter similar.

This temperature spread is also apparent in the way the underlying consumption behaves in Victoria, with the load factor (average demand divided by maximum demand) lower in the southern states.

This all means that, compared to other regions and through no TNSP’s fault, there is less transmission capacity in the southern states on a per unit basis due to the way the ambient temperatures behave across the NEM. While there are already many technologies being employed by TNSPs in Victoria and Tasmania  to maximise the capacities of their transmission networks, such as dynamic line rating using wind monitoring systems and replacing old secondary assets that limit the thermal rating of the lines (e.g., circuit breakers, etc.), there could still be more to be done.

But more importantly, from here on, one thing that we should always consider when putting up a business case for new transmission assets is maximising the utilisation of the lines, maybe by employing new technologies or using better materials.

For more information, please contact us at enquiries@cornwall-insight.com.au.

To keep reading, please log in to your account

Related thinking

Energy storage and flexibility

R1 and L1 revving up the BESS revenues

In our ‘The VFF… Very Fast and Financially rewarding market so far’ Chart of the week, the two new contingency markets, the Very Fast raise contingency FCAS market and the Very Fast lower contingency FCAS, were analysed and demonstrated the high participation of big batteries along with VPPs and DERs....

Low carbon generation

An investigation into REZ capacity factors during Victoria’s dark doldrums

As the grid transitions to much higher levels of renewable penetration, the range of generation outcomes on any given day increases. The worst of these ranges are known as dark doldrums when there is a combination of poor conditions for wind and solar generation, usually a windless day in winter....

Commercial and market outlook

The VFF… Very Fast and Financially rewarding market so far

On 9 October 2023, 1pm (market time), we saw the start of two new contingency FCAS markets. The Very fast raise contingency FCAS market, and the Very fast lower contingency FCAS. Upon commencement of the VF FCAS market, a commissioning period of two weeks with an initial max requirement of...

Commercial and market outlook

Is the sun setting on utility solar?

The Federal Government has legislated emissions reductions of 43% below 2005 levels by 2030. Sourcing electricity from renewable technologies is fundamental to meeting this, with a much-publicised target of 82% renewables in the grid by 2030 – up from a current value of 38% over the last year. Fortunately, the...

Commercial and market outlook

The Very Fast FCAS market is about to commence – a look at a possible time-of-day profile for R1

On 9 October 2023, 1pm (market time), the dispatch of the new Very Fast (VF) FCAS market in the NEM will commence and will add two new markets for contingency FCAS, Raise 1 (R1) and Lower 1 (L1). AEMO has released a final industry go-live plan to keep track of...

Low carbon generation

“Ooh, a storm is threatening, My very [interconnection] today”: Can states utilise interconnection to share wind resources?

Penetration of renewables continues to dominate the energy news, as we saw renewables as a proportion of total demand reach new heights this week to a new record of ~70% penetration. In light of this continuing march toward a renewable-dominated grid (building on some analysis we did in Chart of...

Energy storage and flexibility

How long is the ‘Golden time of day’ for batteries?

A key part of the business case for grid-scale standalone batteries is the arbitrage opportunity between low daytime wholesale prices (when renewable energy generation from solar is plentiful) and high evening prices (when the sun goes down and household demand ramps up quickly). The share of battery revenue coming from...

Low carbon generation

MLF changes in NSW in the past decade

MLF, short for Marginal Loss Factor, represents the portion of electricity losses that occur along the transmission network between a connection point and the Regional Reference Node (RRN). Within the NEM, the MLF serves as a metric to quantify these losses along the network, playing a pivotal role in determining...